sankelux ×

On Grid Inverter SMA Sunny Tripower 25000TL





Harga Total:

Share:

Efficient

  • Maximum efficiency of 98.4%

Safe

  • DC surge arrester (SPD type II) can be integrated

Flexible

  • DC input voltage of up to 1000 V
  • Multistring capability for optimum system design
  • Optional display

Innovative

  • Cutting-edge grid management func-tions with Integrated Plant Control
  • Reactive power available 24/7 (Q on Demond 24/7)


SPESIFIKASI

Input ( DC )

Max. Generator power    : 45000 Wp

DC rated power                        : 25550 W

Max. Input voltage         : 1000 V

MPP voltage / rated input voltage     : 390 V to 800 V / 600 V

Min. Input voltage / start input voltage      : 150 V / 188 V

Max. Input current input A / input B       : 33 A / 33 A

Number of independent MPP inputs / strings per MPP input    : 2 / A:3; B:3

 

Output ( AC )

Rated power ( at 230 V, 50 Hz )     : 25000 W

Max. AC apparent power       : 25000 VA

Ac nominal voltage     : 3 / N / PE; 220 V / 380 V

                                          3 / N / PE; 230 V / 400 V

                                          3 / N / PE; 240 V / 415 V

AC voltage range    :  180 V to 280 V

AC grid frequency / range   : 50 Hz / 44 Hz to 55 Hz

                                                 : 60 Hz / 54 Hz to 65 Hz

Rated power frequency / rated grid voltage    : 50 Hz / 230 V

Max.output current / rated output current     : 36.2 A / 36.2 A

Power factor at rated power / adjustable displacement power factor     : 1 / 0 overexcited to 0 underexcited

THD    : ≤ 3%

Feed-in phases / connection phases   : 3 / 3

 

Efficiency

Max.efficiency / European efficiency    : 98.4% / 98.1%

 

Protective devices

DC-side disconnection device    :

Ground fault monitoring / grid monitoring    : • / •

DC surge arrester (Type II ) can be integrated      : º

DC reverse polarity protection / AC short-circuit current capability / galvanically isolated     : • / • / -

All-pole sensitive residual-current monitoring unit  :  

Protection class (according to IEC 62109-1 ) / overvoltage category (according to IEC 62109-1 )        : I / AC: III; DC:II

 

General data

Dimensions (W / H / D )    : 661 / 682 / 264 mm (26.0 / 26.9 / 10.4 inch)

Weight     : 61 kg (134.48Ib )

Operating temperature range    : -25°Cto+60°C (-13°F to +140 °F )

Noise emission (typical)   : 51 dB (A)

Self-comsumption (at night)     

1
2